表妺好紧竟然流水了在线观看_亚洲熟妇av一区二区三区_国产精品门_精品久久久久久无码人妻

產品列表PRODUCTS LIST

首頁>產品中心>>蓄電池在線測試維護系統>LYDCS-6000直流接地報警儀
LYDCS-6000直流接地報警儀

發布時間:2023-11-13

簡要描述:

LYDCS-6000直(zhi)流(liu)接地(di)報警儀:內(nei)部提供可(ke)調直(zhi)流(liu)電源模(mo)塊,即可(ke)以(yi)模(mo)擬直(zhi)流(liu)系統,將被測(ce)(ce)裝置脫離原(yuan)系統進行校驗(yan),也可(ke)以(yi)在原(yuan)系統上對被測(ce)(ce)絕(jue)緣檢測(ce)(ce)設備進行校驗(yan)。

在線留言
LYDCS-6000直流接地報警儀

一、LYDCS-6000直流接地報警儀概述(shu)

在原有產(chan)品(pin)的(de)基礎上進(jin)行(xing)技(ji)術創新和(he)提(ti)(ti)升。提(ti)(ti)高(gao)了(le)(le)裝置的(de)測量精度和(he)抗電(dian)(dian)(dian)(dian)容干擾(rao)的(de)能(neng)力。在性能(neng)指標(biao)的(de)適(shi)應性、調試的(de)方便性及(ji)運(yun)行(xing)的(de)可(ke)靠性方面均(jun)處于(yu)國(guo)(guo)內水平。裝置*利用了(le)(le)信(xin)號(hao)相位鎖定(ding)、超前校正及(ji)跟蹤(zong)積(ji)木式結構等(deng)技(ji)術,從根本上解決了(le)(le)判(pan)斷數據(ju)(ju)不全(quan)、選線不準(zhun)等(deng)弊(bi)病(bing)。且根據(ju)(ju)2011年12月(yue)國(guo)(guo)家電(dian)(dian)(dian)(dian)網(wang)(wang)公司(si)(si)制(zhi)定(ding)的(de)《十八項國(guo)(guo)家電(dian)(dian)(dian)(dian)網(wang)(wang)公司(si)(si)十八項電(dian)(dian)(dian)(dian)網(wang)(wang)重大反事故(gu)措施》中的(de)第(di)五項“防止變(bian)電(dian)(dian)(dian)(dian)站全(quan)停及(ji)重要客(ke)戶停電(dian)(dian)(dian)(dian)事故(gu)"中明確(que)提(ti)(ti)出了(le)(le)原有的(de)直(zhi)流(liu)電(dian)(dian)(dian)(dian)源(yuan)系(xi)統(tong)絕緣監測裝置,要求增加交(jiao)流(liu)竄(cuan)直(zhi)流(liu)故(gu)障的(de)測記和(he)報警功能(neng)。本裝置采用實時(shi)跟蹤(zong)信(xin)息零處理技(ji)術,解決了(le)(le)交(jiao)流(liu)信(xin)號(hao)竄(cuan)入(ru)直(zhi)流(liu)故(gu)障的(de)測記和(he)報警,是(shi)作為直(zhi)流(liu)系(xi)統(tong)逐(zhu)步改造提(ti)(ti)升的(de)設備。廣泛適(shi)用于(yu)電(dian)(dian)(dian)(dian)力、石化、冶金、郵電(dian)(dian)(dian)(dian)、鐵路等(deng)行(xing)業發電(dian)(dian)(dian)(dian)廠及(ji)變(bian)電(dian)(dian)(dian)(dian)站。是(shi)一種(zhong)提(ti)(ti)高(gao)電(dian)(dian)(dian)(dian)網(wang)(wang)自(zi)動化管理水平、確(que)保安全(quan)運(yun)行(xing)及(ji)故(gu)障準(zhun)確(que)定(ding)位的(de)智(zhi)能(neng)儀器(qi)

公司本著(zhu)“質(zhi)(zhi)量(liang)(liang)*,以質(zhi)(zhi)為(wei)根"的生產(chan)理(li)(li)念,嚴格(ge)貫徹 ISO9001 質(zhi)(zhi)量(liang)(liang)管(guan)理(li)(li)體(ti)(ti)系,決心(xin)為(wei)顧(gu)客提供zui為(wei)優質(zhi)(zhi)的產(chan)品(pin)。公司憑借(jie)先進的科學管(guan)理(li)(li)理(li)(li)念、雄厚(hou)的生產(chan)技(ji)術力(li)量(liang)(liang)、完善(shan)的售后服務、嚴格(ge)的質(zhi)(zhi)量(liang)(liang)管(guan)理(li)(li),獲(huo)(huo)得了ISO9001 質(zhi)(zhi)量(liang)(liang)管(guan)理(li)(li)體(ti)(ti)系認證(zheng)證(zheng)書、計量(liang)(liang)合格(ge)證(zheng)證(zheng)書等多(duo)項證(zheng)書,榮獲(huo)(huo)“上海市(shi)"、“上海市(shi)守(shou)合同重信譽單(dan)位"、“ 全(quan)國電(dian)(dian)力(li)行(xing)業設備選型采購推(tui)薦產(chan)品(pin)"等稱號,是“中國電(dian)(dian)力(li)設備管(guan)理(li)(li)協會(hui)會(hui)員"及“全(quan)國電(dian)(dian)力(li)行(xing)業設備管(guan)理(li)(li)戰略合作伙伴單(dan)位"。

二、LYDCS-6000直流接地報警儀整機測(ce)量原理說明

根據直流系統的特(te)殊性(xing),本裝置的測量從測量內容(rong)區分(fen),可(ke)分(fen)為四大(da)部(bu)分(fen),一是(shi)母線監測,二是(shi)分(fen)支回(hui)路(lu)查巡(xun),三是(shi)交流竄直流監與(yu)報警,直流系統交流成份(fen)紋波的監測。

2.1直流母線監測

2.1.1 在直流系統中(zhong),分(fen)別(bie)從(cong)橋網(wang)絡A和橋網(wang)絡B讀(du)取X和Y兩個直流中(zhong)心對地(di)電壓值。

見圖-

              ◎ U 為(wei)直流(liu)系(xi)統(tong)母線(xian)電壓            ◎ U+為(wei)直流(liu)系(xi)統(tong)母線(xian)正(zheng)極對(dui)地電壓

              ◎ U-為(wei)直流系統母(mu)線負極(ji)對(dui)地電壓   ◎ R+為(wei)直流系統母(mu)線正極(ji)對(dui)地電阻

              ◎ R-為直流系統母線負極對地電阻   ◎ X為電橋網絡A直流中(zhong)點對地電壓

              ◎ Y為電橋網絡B直流中點對地(di)電壓

圖(tu)一

2.1.2根據(ju)電(dian)(dian)(dian)路基(ji)本原理分(fen)析(xi),要準(zhun)確求(qiu)(qiu)出(chu)正對(dui)地電(dian)(dian)(dian)阻R+和負對(dui)地電(dian)(dian)(dian)阻R-,必建(jian)立(li)兩(liang)組獨立(li)的(de)電(dian)(dian)(dian)橋網(wang)絡(luo)方程,將其(qi)聯立(li)求(qiu)(qiu)解,才能真正求(qiu)(qiu)出(chu)兩(liang)個電(dian)(dian)(dian)阻R+和R-的(de)電(dian)(dian)(dian)阻值(zhi)。R1、R2、R分(fen)別組成電(dian)(dian)(dian)橋網(wang)絡(luo),R1≠R2為常量(liang),我們充分(fen)利用兩(liang)個不(bu)平衡橋網(wang)絡(luo)A和網(wang)絡(luo)橋B。可(ke)以(yi)導出(chu)絕緣電(dian)(dian)(dian)阻R+和R-僅(jin)與母線(xian)(xian)電(dian)(dian)(dian)壓及(ji)測量(liang)值(zhi)“X"與“Y"有關(guan)。經電(dian)(dian)(dian)腦編程分(fen)別計(ji)算出(chu)R+與R-的(de)數(shu)值(zhi),同時也(ye)可(ke)以(yi)計(ji)算出(chu)母線(xian)(xian)正端對(dui)地電(dian)(dian)(dian)壓U+與母線(xian)(xian)對(dui)地電(dian)(dian)(dian)壓U-值(zhi)。結構原理如(ru)圖(tu)一所示。

2.2支回路查巡,故(gu)障定位,報警。

主(zhu)機(ji)(ji)中配有大(da)功率電(dian)(dian)(dian)阻做為電(dian)(dian)(dian)橋(qiao)(qiao),檢(jian)測支路(lu)時(shi)定時(shi)啟動電(dian)(dian)(dian)橋(qiao)(qiao)電(dian)(dian)(dian)阻信(xin)號接至直流(liu)系統的(de)(de)(de)正負極與(yu)地(di)之間(jian)。利用電(dian)(dian)(dian)阻電(dian)(dian)(dian)橋(qiao)(qiao)之間(jian)的(de)(de)(de)轉換,不同(tong)的(de)(de)(de)接地(di)電(dian)(dian)(dian)阻與(yu)投入的(de)(de)(de)電(dian)(dian)(dian)橋(qiao)(qiao)電(dian)(dian)(dian)阻之間(jian)的(de)(de)(de)并(bing)聯(lian),產(chan)生(sheng)不同(tong)對(dui)地(di)電(dian)(dian)(dian)壓,產(chan)生(sheng)了不同(tong)的(de)(de)(de)接地(di)漏電(dian)(dian)(dian)流(liu),安裝于各支路(lu)的(de)(de)(de)傳(chuan)感器檢(jian)測每(mei)個(ge)支路(lu)漏電(dian)(dian)(dian)流(liu)。工作原理見(圖二(er))所示。如果支路(lu)有電(dian)(dian)(dian)阻接地(di)、交流(liu)竄入故障(zhang)(zhang)、直流(liu)互(hu)竄故障(zhang)(zhang)的(de)(de)(de)支路(lu)信(xin)號、對(dui)于故障(zhang)(zhang)回路(lu)則該支路(lu)上的(de)(de)(de)傳(chuan)感器產(chan)生(sheng)感應電(dian)(dian)(dian)壓,感應電(dian)(dian)(dian)壓的(de)(de)(de)大(da)小與(yu)支路(lu)電(dian)(dian)(dian)阻成反(fan)比(bi)。感應電(dian)(dian)(dian)壓信(xin)號經模擬選擇開關、放(fang)大(da)、帶通(tong)濾(lv)(lv)波、相位比(bi)較、濾(lv)(lv)波、A/D轉換、送CPU進行數據(ju)處理,再通(tong)過RS485接口轉入主(zhu)機(ji)(ji)。

隨著電網容量的不(bu)斷(duan)擴大,電壓等級的不(bu)斷(duan)提(ti)高(gao)(gao),分(fen)支(zhi)(zhi)回路(lu)也(ye)相(xiang)應的增多,有(you)的變電站(zhan)已(yi)多達500分(fen)支(zhi)(zhi)回路(lu)以(yi)上(shang)。為了滿足這方(fang)面的需(xu)求(qiu),本裝置利(li)用(yong)了總線技(ji)術,采用(yong)分(fen)層分(fen)布式設計。將每16回路(lu)增加一個采集模(mo)塊(kuai),這種分(fen)層分(fen)布式的分(fen)散結構(gou)不(bu)需(xu)改變原有(you)的主機結構(gou)。并可以(yi)拓展到512個回路(lu)。采樣(yang)模(mo)塊(kuai)和(he)主機之間利(li)用(yong)RS485接(jie)口實現(xian)并接(jie)。每個模(mo)塊(kuai)地址碼可以(yi)在現(xian)場隨意設定(ding),大大提(ti)高(gao)(gao)了產品的適用(yong)性(xing)和(he)裝置的可靠(kao)性(xing)。

圖二

2.3 交流(liu)竄直(zhi)流(liu)保護(hu),故(gu)(gu)障幅度(du)與(yu)錄波與(yu)波形(xing)分析(xi),竄入支路故(gu)(gu)障定位。

主(zhu)機配置母(mu)(mu)線(xian)交流(liu)電(dian)(dian)(dian)壓檢測(ce)電(dian)(dian)(dian)路(lu),母(mu)(mu)線(xian)通過電(dian)(dian)(dian)容隔直流(liu)、差分(fen)運放、快(kuai)速(su)整(zheng)流(liu)、濾波、高(gao)速(su)AD,實時檢測(ce)母(mu)(mu)線(xian)上的交流(liu)信(xin)號,并反饋至主(zhu)芯片,若(ruo)外部交流(liu)竄入電(dian)(dian)(dian)壓大(da)(da)于所設定的信(xin)號,通過聲光報(bao)(bao)警(jing)及(ji)干(gan)接點輸(shu)出報(bao)(bao)警(jing)相關(guan)(guan)信(xin)息,并啟動了(le)支路(lu)巡查(cha)電(dian)(dian)(dian)路(lu),巡查(cha)電(dian)(dian)(dian)路(lu)確定故障支路(lu)。并記(ji)錄保存本次報(bao)(bao)警(jing)相關(guan)(guan)信(xin)息,大(da)(da)大(da)(da)提高(gao)系統的安全性和可靠性。如圖四。

圖四

2.4 直流(liu)系統中交流(liu)成(cheng)份(紋波)的監測。故障(zhang)報警。

電(dian)(dian)(dian)路采用(yong)耦合、交直(zhi)流分解(jie)等特殊電(dian)(dian)(dian)路處理(li),能實時準確地(di)對直(zhi)流電(dian)(dian)(dian)源紋(wen)(wen)波(bo)含量即紋(wen)(wen)波(bo)電(dian)(dian)(dian)壓(ya)值,計算直(zhi)流中(zhong)的紋(wen)(wen)波(bo)系數,如圖三(san)。

圖三

2.5 直(zhi)流互(hu)竄(cuan)檢測,故障(zhang)定位(wei)與分析。

本(ben)機內置(zhi)(zhi)快速高(gao)精(jing)度(du)檢測電(dian)(dian)(dian)(dian)(dian)路(lu)(lu),實時檢測現(xian)(xian)(xian)(xian)場(chang)兩(liang)(liang)(liang)段(duan)(duan)(duan)母線(xian)(xian)(xian)之(zhi)間的(de)(de)(de)直(zhi)(zhi)流(liu)互竄故(gu)障,并(bing)準確(que)查(cha)找互竄支(zhi)路(lu)(lu),大大提高(gao)系(xi)統的(de)(de)(de)安全性(xing)和(he)可靠性(xing)。為了(le)(le)(le)保證直(zhi)(zhi)流(liu)電(dian)(dian)(dian)(dian)(dian)源(yuan)對(dui)變電(dian)(dian)(dian)(dian)(dian)站安全運(yun)行(xing)需要。常(chang)常(chang)設有(you)兩(liang)(liang)(liang)段(duan)(duan)(duan)獨立(li)的(de)(de)(de)直(zhi)(zhi)流(liu)電(dian)(dian)(dian)(dian)(dian)源(yuan)。同(tong)一變電(dian)(dian)(dian)(dian)(dian)站兩(liang)(liang)(liang)段(duan)(duan)(duan)直(zhi)(zhi)流(liu)是要求分(fen)開獨立(li)運(yun)行(xing),由(you)于接(jie)(jie)線(xian)(xian)(xian)錯誤,設備老化(hua)通常(chang)會造(zao)成(cheng)兩(liang)(liang)(liang)段(duan)(duan)(duan)母線(xian)(xian)(xian)發(fa)生了(le)(le)(le)電(dian)(dian)(dian)(dian)(dian)氣(qi)上的(de)(de)(de)連(lian)接(jie)(jie),出現(xian)(xian)(xian)(xian)了(le)(le)(le)兩(liang)(liang)(liang)段(duan)(duan)(duan)母線(xian)(xian)(xian)手(shou)拉手(shou)現(xian)(xian)(xian)(xian)象。現(xian)(xian)(xian)(xian)有(you)的(de)(de)(de)直(zhi)(zhi)流(liu)系(xi)統是采(cai)用兩(liang)(liang)(liang)個(ge)電(dian)(dian)(dian)(dian)(dian)橋監測各自的(de)(de)(de)母線(xian)(xian)(xian),兩(liang)(liang)(liang)段(duan)(duan)(duan)母線(xian)(xian)(xian)出現(xian)(xian)(xian)(xian)了(le)(le)(le)電(dian)(dian)(dian)(dian)(dian)氣(qi)上的(de)(de)(de)連(lian)接(jie)(jie)也說(shuo)是會出現(xian)(xian)(xian)(xian)我(wo)們常(chang)說(shuo)的(de)(de)(de)“兩(liang)(liang)(liang)點(dian)接(jie)(jie)地(di)現(xian)(xian)(xian)(xian)象"。兩(liang)(liang)(liang)點(dian)接(jie)(jie)地(di)現(xian)(xian)(xian)(xian)象常(chang)常(chang)會對(dui)變電(dian)(dian)(dian)(dian)(dian)站的(de)(de)(de)繼(ji)電(dian)(dian)(dian)(dian)(dian)保護正(zheng)常(chang)運(yun)行(xing)造(zao)成(cheng)一定的(de)(de)(de)危險。我(wo)們利用了(le)(le)(le)現(xian)(xian)(xian)(xian)有(you)直(zhi)(zhi)流(liu)接(jie)(jie)地(di)裝置(zhi)(zhi)的(de)(de)(de)技(ji)(ji)術升級,將電(dian)(dian)(dian)(dian)(dian)橋電(dian)(dian)(dian)(dian)(dian)路(lu)(lu)的(de)(de)(de)智能(neng)化(hua)技(ji)(ji)術與支(zhi)路(lu)(lu)巡(xun)查(cha)電(dian)(dian)(dian)(dian)(dian)路(lu)(lu)進(jin)(jin)(jin)行(xing)充分(fen)的(de)(de)(de)結合(he),成(cheng)功解決了(le)(le)(le)直(zhi)(zhi)流(liu)系(xi)統兩(liang)(liang)(liang)段(duan)(duan)(duan)母線(xian)(xian)(xian)出現(xian)(xian)(xian)(xian)了(le)(le)(le)電(dian)(dian)(dian)(dian)(dian)氣(qi)上的(de)(de)(de)連(lian)接(jie)(jie),也就是發(fa)生了(le)(le)(le)手(shou)接(jie)(jie)手(shou)的(de)(de)(de)兩(liang)(liang)(liang)點(dian)接(jie)(jie)地(di)進(jin)(jin)(jin)行(xing)了(le)(le)(le)告警,并(bing)通過(guo)支(zhi)路(lu)(lu)巡(xun)查(cha)定位,準確(que)地(di)查(cha)找發(fa)生兩(liang)(liang)(liang)段(duan)(duan)(duan)直(zhi)(zhi)流(liu)母線(xian)(xian)(xian)互竄的(de)(de)(de)回(hui)路(lu)(lu)。我(wo)們將兩(liang)(liang)(liang)臺(tai)測量的(de)(de)(de)直(zhi)(zhi)流(liu)絕(jue)緣(yuan)監察(cha)裝置(zhi)(zhi)通過(guo)測量與通迅(xun)技(ji)(ji)術,進(jin)(jin)(jin)行(xing)數據分(fen)析,進(jin)(jin)(jin)行(xing)了(le)(le)(le)定位,有(you)效地(di)查(cha)找發(fa)生直(zhi)(zhi)流(liu)互竄接(jie)(jie)地(di)的(de)(de)(de)回(hui)路(lu)(lu)。

發(fa)生直(zhi)流互竄的(de)主要歸納為有(you)五種工(gong)作(zuo)方式:

現象(xiang)一、*段(duan)母線負端與第二段(duan)母線負互竄。

現象二: *段(duan)母線(xian)正(zheng)和第(di)二段(duan)母線(xian)正(zheng)互竄.

現(xian)象三:*段(duan)母(mu)線正(zheng)(zheng)和第二(er)段(duan)母(mu)線正(zheng)(zheng),*段(duan)母(mu)線負(fu)和第二(er)段(duan)母(mu)線負(fu)同時(shi)互(hu)竄

現象四:*段(duan)母(mu)線(xian)(xian)負端(duan)和(he)第二段(duan)母(mu)線(xian)(xian)正(zheng)端(duan)互竄(cuan),或*段(duan)母(mu)線(xian)(xian)正(zheng)端(duan)和(he)第二段(duan)母(mu)線(xian)(xian)負端(duan)互竄(cuan)。

 

三、LYDCS-6000功能特點

本裝置采用Cortex-M3內核(he)的STM32芯(xin)片為主控芯(xin)片,集(ji)成度高,抗干擾能力強(qiang),運(yun)行速度快,功(gong)耗低(di)。

3.1 操作界面基于菜(cai)單式的人性化設(she)計。

3.2相關(guan)(guan)的(de)所有(you)參數均可通過菜單進(jin)行(xing)設置,相關(guan)(guan)的(de)所有(you)報警均通過聲光(guang)輸(shu)出(chu)和相應(ying)的(de)干接點輸(shu)出(chu)。

3.3準確檢測直(zhi)流(liu)電(dian)壓、模(mo)塊狀態(tai)、直(zhi)流(liu)絕緣及接地(di)(di)選線(xian)為;精(jing)確區(qu)分母(mu)線(xian)接地(di)(di)、支路接地(di)(di),并顯示接地(di)(di)電(dian)阻阻值(zhi);自動分辨兩(liang)條或兩(liang)條以上支路同時接地(di)(di)的故障(zhang)等(deng)。

3.4可隨時操作界面進入全部支(zhi)路(lu)的巡檢操作,以觀(guan)察(cha)全部支(zhi)路(lu)的接地狀況。

3.5 可隨(sui)時(shi)操(cao)作界面進入全(quan)部(bu)(bu)支路的(de)單(dan)檢(jian)(jian)操(cao)作,分(fen)全(quan)部(bu)(bu)支路單(dan)檢(jian)(jian)(通(tong)過按鍵循環檢(jian)(jian)測(ce))和選(xuan)定支路單(dan)檢(jian)(jian)(通(tong)過按鍵選(xuan)定某一支路檢(jian)(jian)測(ce))。

3.6 保存顯示當(dang)前5次的母線絕緣報(bao)警(jing)記錄。

3.7 提(ti)供檢測2段(duan)母(mu)線的紋波電壓和紋波系數。

3.8 對CT極(ji)性(xing)無*性(xing)要(yao)求(qiu)、無方向要(yao)求(qiu)。

3.9 信號采(cai)集數據采(cai)用RS485接口技術,使數據的有(you)效傳(chuan)輸距離可達 1000米。

3.10裝置(zhi)提供串(chuan)行(xing)數據通訊接(jie)口(RS-232、RS-485)和外(wai)部設備(bei)連系。

3.11 裝(zhuang)置提供100M的以太網接口(kou)。

3.12支路檢(jian)測速度(du)快.巡檢(jian)16路以后的數據時(shi),平均每路巡檢(jian)時(shi)間低于(yu)1秒(miao)。

3.13 本機可以(yi)通過參數設定設置交流竄入報警門限(交流有效值)。

3.14裝置采(cai)用實時(shi)跟蹤信息零處理技術,解決了交流信號(hao)竄入(ru)直流故障(zhang)的(de)測記和報

警。  

3.15采用(yong)彩屏(ping)液(ye)晶(jing)顯示、中文界面、顯示直觀明了(le),并帶(dai)有液(ye)晶(jing)自動(dong)保護功能。

3.16本系統(tong)可提供簡單(dan)的多機連接功能(neng),適用于復雜的多級直(zhi)流系統(tong)中,不(bu)會出

誤報及拒報現(xian)象(xiang)。

3.17 紋波(bo)測量:采用(yong)實時全數字寬帶測量、實時測量全范圍的(de)直流電(dian)源紋波(bo)、電(dian)

壓值、并(bing)計算紋波系數(shu)值,有效記(ji)錄(lu)直流(liu)電源中的(de)交流(liu)含量。

 

四(si)、LYDCS-6000技術性能指(zhi)標

4.1 適應環境溫度:-10℃~+55℃:濕度≤90%

4.2 大(da)氣壓(ya):80-110KPA;

4.3 直流系統電(dian)壓(ya)等級:220Vdc、110Vdc、48Vdc、24Vdc;

4.4裝置(zhi)工作(zuo)電(dian)壓:AC/DC 85-265v

4.5 母線(xian)段數(shu):二段

4.6 繼電器接點電流:DC220V/3A

4.7 母線電壓測(ce)量精度:±0.5%

4.8 母線(xian)絕緣電(dian)阻測(ce)量精度(du):0-5KΩ*.1KΩ

                           5-50KΩ誤差≤5%

                           50-100KΩ誤(wu)差(cha)≤10%

4.9 繼電器動(dong)作報警時間:    ≤2秒

4.10 支路絕緣電阻測量精度:0.5-10KΩ誤差≤15%

 10-25KΩ誤差≤20%

4.11 交(jiao)流竄(cuan)入電壓測量范(fan)圍:0-300V

4.12  交流竄入電壓(ya)測(ce)量精度:≤1%

4.13 紋波測量范圍:0-100V

4.14 紋波測(ce)量精度大于1%

4.15裝置功耗:≤30W

4.16 裝置重量(liang):≤8Kg

4.17 外型尺(chi)寸:(長×高×深):360×135×280㎜,

4.18 采集單(dan)元(yuan)外型:155×95×43㎜

 

五、LYDCS-6000產品(pin)圖片

5.1主機(ji)前(qian)面板各部件功能(neng)介紹:見上(shang)圖(tu)所示。

5.1.1按鍵(jian)“上"鍵(jian)、“下"鍵(jian)、“左"鍵(jian)、“右"鍵(jian)、“確(que)定"鍵(jian)、“取消"鍵(jian)。

5.1.2指示燈

電源指示燈(deng):儀器通(tong)上電源時,該燈(deng)亮。

信號指示燈:儀器進入支路檢(jian)測狀態(tai)后,該燈亮。

超壓(ya)報警燈(deng):母線電(dian)壓(ya)超過門限設定值時(shi),該燈(deng)亮。

欠壓(ya)報(bao)警燈:母(mu)線電壓(ya)低于門限設定值時(shi),該燈亮。

絕緣報警燈:母線對地(di)絕緣電阻(zu)低于門限設定值時,該燈亮。

支路報(bao)警燈:支路檢測(ce)時(shi),接地電阻值低(di)于門限(xian)設定值時(shi),該(gai)燈亮。

瞬時接地(di)燈:母線瞬時對(dui)地(di)絕(jue)緣(yuan)電阻值低于門限(xian)設定值時,該燈亮。

 交流串路燈:當有交流竄(cuan)入時,該燈亮。

5.1.3液晶顯示器

中文(wen)顯(xian)示設定參數(shu),母(mu)線監測(ce)數(shu)據及(ji)支路檢(jian)測(ce)數(shu)據等.

5.1.4電源(yuan)開(kai)關(guan)

電源(yuan)開關(guan)置于機(ji)箱后面,置ON時接(jie)通儀器工(gong)作電源(yuan),置OFF時,電源(yuan)切斷。

5.2主機(ji)后(hou)面面板簡介

后(hou)面板上貼有(you)接(jie)線(xian)端子功能表,見下(xia)圖所示。其中(zhong)故障報(bao)警繼電(dian)(dian)(dian)器輸出為(wei)常閉(bi)觸點(dian)(dian),當儀(yi)器正(zheng)常工作時(shi),該(gai)繼電(dian)(dian)(dian)器觸點(dian)(dian)斷開(kai);當儀(yi)器發生故障時(shi),該(gai)繼電(dian)(dian)(dian)器觸點(dian)(dian)閉(bi)合(he)。其它(ta)報(bao)警繼電(dian)(dian)(dian)器輸出均為(wei)常開(kai)觸點(dian)(dian),只有(you)報(bao)警輸出時(shi),相(xiang)應的繼電(dian)(dian)(dian)器觸點(dian)(dian)才閉(bi)合(he)。

六、LYDCS-6000通(tong)電前檢查

6.1裝(zhuang)置到貨(huo)后(hou),首先應檢查包(bao)裝(zhuang)箱上的產品(pin)登(deng)記單與裝(zhuang)置箱體(ti)上的質(zhi)量檢驗合(he)格證,并確認與訂貨(huo)*。

6.2打開裝置機箱對裝置各部件進(jin)行檢(jian)查(cha),確定各部件有(you)無松動(dong)及損壞(huai)現象,檢(jian)查(cha)有(you)關電纜線(xian)連接(jie)是否可靠(kao)。

6.3核對裝置(zhi)工作電源電壓(ya)和現場電壓(ya)是否(fou)相符。

6.4上(shang)述(shu)各項(xiang)檢查完畢方可通電試驗。

 

七、LYDCS-6000安(an)裝

7.1本(ben)裝置可單獨安(an)(an)放在工(gong)作臺或(huo)安(an)(an)裝在直流(liu)屏柜(ju)內。系統為了(le)適應(ying)不(bu)同的(de)用戶,在外觀設計(ji)時選用了(le)兩(liang)種機(ji)型,4U的(de)機(ji)型里(li)面安(an)(an)裝了(le)兩(liang)個采(cai)樣(yang)模塊,小機(ji)型里(li)面沒有安(an)(an)裝采(cai)樣(yang)部件。具體安(an)(an)裝尺寸見圖五。

            圖(tu)五(wu)

7.2互感(gan)器安裝(zhuang)

7.2.1互感器應安(an)裝在支(zhi)路距母線的zui近端(duan)(zui后(hou)安(an)裝在分支(zhi)路空氣開(kai)關或熔絲(si)之間)。

7.2.2常見(jian)的規格有內徑為φ18、φ44、φ90及K20四(si)種(zhong)見(jian)圖(tu)六(三種(zhong))。

7.2.3互感器的一(yi)個接線端子(zi)(zi)連接在采樣模(mo)塊(kuai)的信號輸入(ru)支路(lu)端子(zi)(zi)上而(er)另一(yi)個接線端子(zi)(zi)連接在采樣模(mo)塊(kuai)的接地輸入(ru)端子(zi)(zi)上。

圖六(liu)

7.3采集模塊的安裝(zhuang):

按回(hui)路的(de)(de)(de)需要(yao)增(zeng)加相應的(de)(de)(de)互感器和采(cai)集(ji)模(mo)(mo)塊,各采(cai)樣(yang)模(mo)(mo)塊之間采(cai)用(yong)≥0.5平方毫米(mi)的(de)(de)(de)導線(xian)相連(lian)接(jie)。各分支路互感器接(jie)在采(cai)集(ji)模(mo)(mo)塊的(de)(de)(de)信號(hao)輸入端(duan)(duan)。(各采(cai)樣(yang)模(mo)(mo)塊的(de)(de)(de)輸入端(duan)(duan)的(de)(de)(de)地(di)線(xian)是獨立的(de)(de)(de),不和大地(di)連(lian)接(jie))參(can)照圖五

7.4 ;主從機(ji)(多(duo)機(ji)系統運行)部分安裝簡要(yao)說明(ming):

7.4.1 主從(cong)機之間(jian)通(tong)過RS485通(tong)訊連(lian)接,即(ji)每臺機器(qi)后面(mian)面(mian)板的第39(RS485A)、第40(RS485B)端子并聯。

7.4.2 所有模塊均通過五芯線(xian)連至主(zhu)機后(hou)面面板第31-35端子。

7.5采樣模(mo)塊

7.5.1采(cai)(cai)樣模塊的(de)使用(yong),采(cai)(cai)樣模塊是本裝置拓展(zhan)(zhan)采(cai)(cai)樣回(hui)路的(de)關鍵(jian)部件(jian),是拓展(zhan)(zhan)多級聯機(ji)的(de)入口(kou)。

7.5.2采樣模(mo)塊的編(bian)碼:采樣模(mo)塊編(bian)號采用8421方式,以先后順(shun)序從(cong)1到(dao)99。

7.5.3采樣(yang)(yang)模塊的編碼方(fang)法:(安裝面向下,文(wen)字標志面向上)。8位撥碼開關(guan)分別(bie)表示(shi)十進制(zhi)的個位(1.2.3.4),和(he)十位(5.6.7.8),每一(yi)位按照二進制(zhi)方(fang)式計算,直到9。各位開關(guan)在(zai)靠近NO的字樣(yang)(yang)邊(bian)是(shi)0,選中的數字鍵向下有效。所以在(zai)使(shi)用時要注意采樣(yang)(yang)模塊的編碼要按順序編制(zhi),檢查無誤(wu)后(hou)才能通(tong)電(dian)運行(xing)。如要設置第63塊,見下表:

7.5.4采樣模塊是裝(zhuang)置的(de)(de)(de)子(zi)系統,它的(de)(de)(de)地(di)(di)線(xian)(xian)是獨(du)立的(de)(de)(de),所以各(ge)個互(hu)感器的(de)(de)(de)接(jie)地(di)(di)點應(ying)接(jie)在所屬模塊的(de)(de)(de)接(jie)地(di)(di)點上。以防相互(hu)干擾,采樣模塊的(de)(de)(de)地(di)(di)線(xian)(xian)不(bu)和大地(di)(di)連接(jie).采集模塊超過4個需(xu)要加一個12V的(de)(de)(de)電源.用戶在使(shi)用時請注(zhu)意。

7.5.5采樣模塊和主機的(de)連線可參考連線圖七。